SGPLS · Electric shock, Fire
Product: Residual-current circuit braker · GENROON · C32
Category: Electrical appliances and equipment · Cyprus
Hazard: The RCBO does not trip in case of sudden appearance of residual current. A person that touches a part of the electrical installation equipped with this RCBO can receive an electric shock. Moreover, the product can overheat, increasing the risk of fire. The product does not comply with the requirements of the Low Voltage Directive nor with the European standards EN 61009-1 and EN 61009-2-2.
Official action: Type of economic operator taking notified measure(s): Importer Category of measure(s): Recall of the product from end users Date of entry into force: 17/12/2024